Various Methods for Measurement of Resistive Leakage Current of Metal Oxide Surge Arrester
Author(s) -
Samruddhi Shaha,
Yaseen Khan Anwar Khan Dakhani
Publication year - 2021
Publication title -
international journal of scientific research in science, engineering and technology
Language(s) - English
Resource type - Journals
eISSN - 2395-1990
pISSN - 2394-4099
DOI - 10.32628/ijsrset218374
Subject(s) - surge arrester , lightning arrester , leakage (economics) , surge , impulse (physics) , resistive touchscreen , electrical engineering , current (fluid) , materials science , forensic engineering , engineering , physics , quantum mechanics , economics , macroeconomics
Metal Oxide Surge Arrester (MOSA) does not require any ordinary maintenance. But MOSA is get affected from ageing due to the effect of discharging impulse currents, uneven heating and internal partial discharges. A leading cause of deterioration is ingress of moisture. The degradation of MOSA also correlated with the ageing level of the arrester. This is called degradation under surge. The ageing level with the degradation of MO surge arrester or the leakage current of the surge arrester is related to each other. The leakage current is directly proportional to the ageing level. If the ageing level is raise, the leakage current also will increase. So, various methods for determination of the condition of ZnO surge arrester by means of measurement of the arrester leakage current are discussed. A MSCM method, which is based on leakage current of the surge arrester presented. The measuring instrument Leakage Current Monitor is also discussed.