z-logo
open-access-imgOpen Access
ANALISA GANGGUAN HUBUNG SINGKAT DENGAN MENGGUNAKAN ETAP 12.6.0 PADA PT X
Author(s) -
Badaruddin Badaruddin
Publication year - 2017
Publication title -
jurnal teknik
Language(s) - English
Resource type - Journals
eISSN - 2581-0006
pISSN - 2302-8734
DOI - 10.31000/jt.v5i1.338
Subject(s) - computer science
ConstructionofcoalhandlingfacilityPTXdemandingtheneedforan analysisofthe equipmentratingcircuitbreaker(CircuitBreaker),sothatthe CircuitBreaker(CB)can secure thepowersystemagainstharmfulinterference,especiallyinterference symmetrical short-circuitthree-phase.Foritwas doneastudyofshortcircuitintheelectricpower system.Calculationofthesymmetricalshort-circuitfaultcurrentis basedonsoftware simulationETAP 12.6. The conclusionisthatthe biggestfaultcurrent. The results obtainedforsymmetricalthree-phasedisorders,thegreatestdisruptionoccursinLV MCCbus(400V) withinitialsymmetricalfaultcurrent(I "k) amountedto62.170kA,the maximum short circuit current (Ip)of 130.450 kA. Keywords: power systemanalysis, 3-phaseshortcircuit, ETAP.