Thermal modelling of oil-filled power transformer TM - 160/10
Author(s) -
N Nguyen Tien,
К. Х. Гильфанов
Publication year - 2019
Publication title -
izvestiâ vysših učebnyh zavedenij. problemy ènergetiki
Language(s) - English
Resource type - Journals
eISSN - 2658-5456
pISSN - 1998-9903
DOI - 10.30724/1998-9903-2019-21-5-141-151
Subject(s) - transformer , distribution transformer , materials science , transformer oil , energy efficient transformer , thermal , mechanics , electrical engineering , isolation transformer , voltage , thermodynamics , engineering , physics
The results of modeling the thermal characteristics of the dry and oil-filled power transformer TM-160/10 in idle and short circuit modes are presented. The electrical, geometric and thermal characteristics of the TM-160/10 transformer are determined. Computer modeling is performed in the software package ANSYS 17.1. The 2D distributions of temperature and density of heat flows in the transformer in the longitudinal and transverse sections are determined. It is shown that the use of transformer oil for cooling the transformer significantly reduces the temperatures in the active part. The temperature distribution occupies the range of 67-91 °С . Accordingly, the temperature of the most heated part is 91 °C and also corresponds to the low voltage winding. The dependence of the most heated point of the transformer on the operating mode was studied. A formula is proposed for calculating the maximum temperature of a transformer as a function of power loss.