Subject(s) - transformer , polymerization , materials science , degree (music) , composite material , electrical engineering , engineering , voltage , physics , polymer , acoustics
The paper presents the results of research and analysis of literature data on the paper insulation's thermal aging. An exponential decrease in the degree of polymerization of paper insulation from the aging time is established, at the starting time of transformers’ operation the aging rate of paper insulation is maximal and after that its slowing down. It was found out that the degree of polymerization at the starting time of the transformer's operation can be in the range of 900 units, this is due to its drying during the manufacturing process.