Physical and mathematical modeling of transients in a synchronous generator utilizing synchronized phasor measurements
Author(s) -
V. R. Rafikov,
И. Э. Иванов,
A.A. Bratoliubov
Publication year - 2021
Publication title -
vestnik igèu
Language(s) - English
Resource type - Journals
ISSN - 2072-2672
DOI - 10.17588/2072-2672.2021.3.022-032
Subject(s) - phasor , phasor measurement unit , transient (computer programming) , stator , control theory (sociology) , flux linkage , electric power system , fault (geology) , emtp , synchronous motor , matlab , permanent magnet synchronous generator , engineering , power (physics) , computer science , voltage , induction motor , electrical engineering , physics , direct torque control , control (management) , quantum mechanics , artificial intelligence , seismology , geology , operating system
There have been quite a few attempts to compute synchronous generator parameters based on voltage and current synchrophasors taken under power system transients. However, we have not seen any publications with thorough analysis as to how soon the phasor measurement unit reacts to disturbance conditions, which components of the transient are filtered out and which are passed through, as well as what the total vector error is. The goal of this research is to determine all of these characteristics of a phasor measurement unit when playing back transient oscillograms for a stator short circuit obtained through mathematical modeling. The transient oscillograms have been derived via both a full Park-Gorev system of flux linkage equations as well as the MATLAB/Simulink Synchronous Machine block. Physical modeling was then conducted via a real-time digital simulator (RTDS) along with a dedicated phasor measurement unit ENIP-2 (PMU), and the stator current phasors were recorded. Our analysis has shown that both RTDS and ENIP-2 (PMU) almost entirely filter out the exponentially decaying DC component of the fault current while closely following the periodical signal envelope. The total vector error has been estimated to become below 1–2 % after around 0,02–0,03 s into the fault when selecting the “P” class filters according to IEEE C37.118. We have come to a conclusion that synchrophasor measurements under power system disturbances could be utilized for estimating the synchronous, transient, and subtransient generator parameters. The selected synchronous machine model in the form of flux linkage equations is correct, as the obtained transient oscillograms are exactly the same as those produced by Simulink. “P” class phasor measurements can be recommended for representing transients in the stator circuit of a synchronous generator. The results of this investigation are meant to be employed for synchronous machine parameter estimation based on phasors sourced from RTDS and, hopefully, from phasor measurement units installed at power plants.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here