RESEARCH INFLUENCE OF ANALYTICALLY CALCULATED AND REAL ELECTRICAL LOAD OF MULTFLAT HOUSING IN CHOICE OF POWER OF INTER QUARTERLY SUBSTATIONS
Author(s) -
Anatolii Bondarchuk,
Evgenija P. Nechiporuk
Publication year - 2020
Publication title -
elektrotehnìčnì ta komp'ûternì sistemi
Language(s) - English
Resource type - Journals
eISSN - 2221-3937
pISSN - 2221-3805
DOI - 10.15276/eltecs.33.109.2020.2
Subject(s) - transformer , electricity , apartment , automotive engineering , reliability engineering , electric potential energy , environmental science , engineering , computer science , electrical engineering , energy (signal processing) , mathematics , civil engineering , voltage , statistics
The studies were conducted on four 216-apartment buildings, which account for a 10 / 0.4 kV substations. Built by spline interpolation in the MathCAD environment, the charts of the electrical load of homes by standard indicators and based on information measurement. Turning the obtained graphs into two stages, the parameters of the rated capacities of the oil transformers 400 and 250 kVA were chosen by their parameters, since the rated power by the standards turned out to be much higher than the actual one. The variant with the TM-250/10 transformer, will save (energy efficiency) by reducing electricity losses during operation about 492,2 tons conditional fuel, in case of electricity loss (economic efficiency), the option is cheaper by UAH 268,2 thousands, which will result in emission reductions (environmental efficiency) of about 163,6 tons.