z-logo
Premium
The risk of airborne cross‐infection in a room with vertical low‐velocity ventilation
Author(s) -
Olmedo I.,
Nielsen P. V.,
Ruiz de Adana M.,
Jensen R. L.
Publication year - 2013
Publication title -
indoor air
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 1.387
H-Index - 99
eISSN - 1600-0668
pISSN - 0905-6947
DOI - 10.1111/j.1600-0668.2012.00794.x
Subject(s) - diffuser (optics) , ventilation (architecture) , thermal manikin , environmental science , personal protective equipment , air change , position (finance) , infection risk , simulation , medicine , computer science , covid-19 , engineering , light source , emergency medicine , mechanical engineering , materials science , thermal insulation , business , physics , pathology , optics , composite material , layer (electronics) , disease , infectious disease (medical specialty) , finance
  Downward flow ventilation systems are one of the most recommended ventilation strategies when contaminants in rooms must be removed and people must be protected from the risk of airborne cross‐infection. This study is based on experimental tests carried out in a room with downward flow ventilation. Two breathing thermal manikins are placed in a room face to face. One manikin’s breathing is considered to be the contaminated source to simulate a risky situation with airborne cross‐infection. The position of the manikins in relation to the diffuser and the location of diffuser in the room as well as the distance between the manikins are being changed to observe the influence of these factors on the personal exposure of the target manikin. The results show that the DWF in different situations often is unable to penetrate the microenvironment generated by the manikins. The downward ventilation system can give an unexpected high level of contaminant exposure of the target manikin, when the distance between the manikins is reduced. Practical Implications Several guidelines recommend the downward ventilation system to reduce the risk of cross‐infection between people in hospital rooms. This study shows that this recommendation should be taken into careful consideration. It is important to be aware of people position, position to other thermal loads in the room, and especially be aware of the distance between people if the exposure to the exhaled contaminants wants to be reduced.

This content is not available in your region!

Continue researching here.

Having issues? You can contact us here