z-logo
Premium
Risk factors in heating, ventilating, and air‐conditioning systems for occupant symptoms in US office buildings: the US EPA BASE study
Author(s) -
Mendell M. J.,
LeiGomez Q.,
Mirer A. G.,
Seppänen O.,
Brunner G.
Publication year - 2008
Publication title -
indoor air
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 1.387
H-Index - 99
eISSN - 1600-0668
pISSN - 0905-6947
DOI - 10.1111/j.1600-0668.2008.00531.x
Subject(s) - hvac , air conditioning , environmental health , odds ratio , ventilation (architecture) , logistic regression , confidence interval , medicine , environmental science , sick building syndrome , indoor air quality , indoor air , odds , air pollutants , environmental engineering , meteorology , air pollution , engineering , geography , ecology , biology , mechanical engineering
Building-related symptoms in office workers worldwide are common, but of uncertain etiology. One cause may be contaminants related to characteristics of heating, ventilating, and air-conditioning (HVAC) systems. We analyzed data from 97 representative air-conditioned US office buildings in the Building Assessment and Survey Evaluation (BASE) study. Using logistic regression models with generalized estimating equations, we estimated odds ratios (OR) and 95% confidence intervals for associations between building-related symptom outcomes and HVAC characteristics. Outdoor air intakes less than 60 m above ground level were associated with significant increases in most symptoms: e.g. for upper respiratory symptoms, OR for intake heights 30 to 60 m, 0 to <30 m, and below ground level were 2.7, 2.0, and 2.1. Humidification systems with poor condition/maintenance were associated with significantly increased upper respiratory symptoms, eye symptoms, fatigue/difficulty concentrating, and skin symptoms, with OR = 1.5, 1.5, 1.7, and 1.6. Less frequent cleaning of cooling coils and drain pans was associated with significantly increased eye symptoms and headache, with OR = 1.7 and 1.6. Symptoms may be due to microbial exposures from poorly maintained ventilation systems and to greater levels of vehicular pollutants at air intakes nearer the ground level. Replication and explanation of these findings is needed.

This content is not available in your region!

Continue researching here.

Having issues? You can contact us here