Open Access
Studies on Overheating Fault of Disconnecting Switch
Author(s) -
Zhijun Lan,
Yaping Wang,
Jiansheng Wu,
Youwen Fan
Publication year - 2020
Publication title -
iop conference series. materials science and engineering
Language(s) - English
Resource type - Journals
eISSN - 1757-899X
pISSN - 1757-8981
DOI - 10.1088/1757-899x/793/1/012024
Subject(s) - overheating (electricity) , power grid , grid , inner mongolia , engineering , electrical engineering , mechanical engineering , china , power (physics) , geology , geodesy , quantum mechanics , political science , law , physics
This paper mainly presents typical solutions to disconnecting switch overheating and mechanical problems of power grid in Extra High Voltage (EHV). In recent years, many faults have happened in the EHV power grid due to overheating and mechanical problems of disconnecting switches in Inner Mongolia. Dust storm weather and the special structure are main reasons which induced disconnecting switch lower operation reliability. For the overheating problems, the solutions include using conducting metal belt, replacing material of knee-arm wheel and modifying the structure of rolling-contact assembly; for the mechanical problems, the solutions include using dust shield, renovating operating mechanism and decreasing mechanically-driven part. Meanwhile suggestions are proposed as well for the design and application of isolator in the power networks of Western Inner Mongolia and the Northwester China which have similarly peculiar natural environments.