Research on transmission mechanism of harmonics in cable lines
Author(s) -
Ling Pan,
Feng Qian,
Peng Zhang,
Bing Shen,
Ran Chen,
Ping Zeng
Publication year - 2021
Publication title -
iop conference series. earth and environmental science
Language(s) - English
Resource type - Journals
eISSN - 1755-1307
pISSN - 1755-1315
DOI - 10.1088/1755-1315/772/1/012014
Subject(s) - harmonics , harmonic , electrical engineering , electric power transmission , harmonic analysis , power (physics) , engineering , voltage , physics , electronic engineering , acoustics , quantum mechanics
The high cabled rate of urban power grid aggravates the risk of resonance and harmonic amplification. In addition, the system side of DC receiving end urban power grid contains converter station high-power harmonic sources, while the user side contains other nonlinear user harmonic sources. There are two-way conduction characteristics of harmonics in transmission lines. The problem of resonance and harmonic amplification in distribution network is aggravated by high cable ratio. Therefore, the response of the system side injected harmonic voltage at the end of the line and the potential harmonic amplification problem after the user side injected harmonic current are studied respectively. The influence of key factors (line type, length, load rate and power factor) on harmonic propagation is analyzed. The characteristic harmonic of converter station is not amplified and the most severe condition of amplification is summarized. The harmonic limit of the harmonic injection terminal is also proposed.