Simulation Analysis of Ferro resonance of Generator-Transformer Group Shock Tripping
Author(s) -
Dewen Zhang,
Xinyu Wei,
Peiyong Yu,
Yubo Shen,
Haifeng Ma
Publication year - 2021
Publication title -
iop conference series. earth and environmental science
Language(s) - English
Resource type - Journals
eISSN - 1755-1307
pISSN - 1755-1315
DOI - 10.1088/1755-1315/769/4/042092
Subject(s) - overvoltage , transformer , electrical engineering , inductance , tripping , ferroresonance in electricity networks , engineering , voltage , circuit breaker
As a common self-excited oscillation in power systems, ferromagnetic resonance has a great threat to the insulation of electrical equipment due to overvoltage and overcurrent. The magnetizing inductance of electromagnetic voltage transformers has nonlinear characteristics, which tend to saturate the excitation and cause circuit resonance and generate resonance overvoltage. The ferromagnetic resonance overvoltage caused by the saturation of the transformer has greatly affected the safe and stable operation of the power grid. Therefore, it is very necessary to analyze, calculate and simulate the ferromagnetic resonance overvoltage, and to study the measures to eliminate resonance. Through theoretical calculation and simulation analysis of a hydroelectric power plant generator-transformer group reverse transmission impulse tripping fault, the cause of its ferromagnetic resonance was analysed, and relevant operation and maintenance suggestions were put forward to provide a basis for further research.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here