Analysis of the influence of heat source well parameters on pumping temperature of groundwater source heat pump
Author(s) -
Wu Min
Publication year - 2021
Publication title -
iop conference series. earth and environmental science
Language(s) - English
Resource type - Journals
eISSN - 1755-1307
pISSN - 1755-1315
DOI - 10.1088/1755-1315/631/1/012047
Subject(s) - heat pump , coefficient of performance , aquifer , groundwater , thermal , materials science , thermodynamics , heat transfer coefficient , mechanics , heat transfer , heat exchanger , geotechnical engineering , geology , physics
In this paper, MATLAB software is used to simulate the influence of parameters of different heat source wells on pumping temperature in groundwater source heat pump system. The absolute value of horizontal permeability coefficient of aquifer will not affect its pumping temperature, but when the permeability coefficient ratio increases from 1 to 10, the pumping temperature decreases by 1.1°C; When the specific heat capacity increases from 2000 kJ / m3 · °C to 3000 kJ / m3 · °C, the pumping temperature decreases by 0.8 °C; When the degree of thermal dispersion increases from 1m to 3m, the pumping temperature decreases by 0.4°C.