z-logo
open-access-imgOpen Access
Analysis and preventive measures of a shutdown accident caused by high voltage insurance slow melting of a voltage transformer used in excitation system
Author(s) -
Zhunli Qian
Publication year - 2020
Publication title -
iop conference series. earth and environmental science
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.179
H-Index - 26
eISSN - 1755-1307
pISSN - 1755-1315
DOI - 10.1088/1755-1315/512/1/012145
Subject(s) - transformer , electrical engineering , voltage , high voltage , excitation , distribution transformer , voltage drop , materials science , low voltage , engineering
The voltage transformer (TV) excitation system high-voltage fuse is divided into two cases: one is a short-time fast fuse in the high-voltage fuse, and the voltage on the secondary side of the transformer should drop to zero in an instant. The second is that the high-voltage insurance is slowly fused for a long time, and the voltage on the secondary side of the voltage transformer drops slowly, resulting in the excitation system erroneously strong excitation, the terminal voltage rises, the over-excitation protection action chain reaction, and even the accidental trip. In recent years, the shutdown accidents frequently occur in China due to the high voltage insurance slow-melting of excitation voltage transformers. In this paper, the author analyzes the accident caused by the slow melting of TV high voltage insurance for excitation of one-million-kilowatt units in a company, and puts forward some preventive measures.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here