Study on Performance of Ground Source Heat Pump System Based on Active Chilled Beam
Author(s) -
Wei Yu,
Hui Li,
Xiaojie Niu
Publication year - 2019
Publication title -
iop conference series. earth and environmental science
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.179
H-Index - 26
eISSN - 1755-1307
pISSN - 1755-1315
DOI - 10.1088/1755-1315/371/3/032064
Subject(s) - heat pump , coefficient of performance , air source heat pumps , unit (ring theory) , nuclear engineering , air conditioning , inlet , efficient energy use , beijing , beam (structure) , hybrid heat , environmental science , research object , materials science , mechanical engineering , engineering , electrical engineering , structural engineering , mathematics , mathematics education , heat exchanger , china , regional science , political science , law , geography
This paper takes the ground source heat pump unit of a research and development centre in Beijing as the research object. This collected the operation data in the cooling condition and the heating condition respectively. Based on the measured data, this paper calculated the coefficient of performances and the energy efficiency ratio of the unit. The results show that when the active chilled beam is used as the air-conditioning terminal device, the inlet temperature of the heat pump unit is greatly improved. The ground source heat pump unit meets the standard and has a higher energy efficiency ratio; The operation of a single unit is more efficient than that of multiple units at the same time.