This study focuses on the fault ride through capability of HPR1000 NPP in the UK grid and presents a Simulink-based modelling and simulation of the demonstration. The paper firstly introduces the fault ride through requirements of the UK grid, then describes the modelling process and analyses the simplified part accordingly, and finally analyses a three-phase ground fault with a duration of 140ms and a three-phase ground fault with a residual voltage of 85% and a duration of 180 seconds. The results show that the fluctuations of the plant under various fault ride through scenarios meet the requirements of the UK grid indicating the plant has fault ride through capability in the UK grid.