z-logo
open-access-imgOpen Access
Research on hidden dangers of oil-flow relay in HVDC converter transformer
Author(s) -
Kun Chen,
Qixin Yao,
Zengrui Huang,
Ting Wang
Publication year - 2021
Publication title -
journal of physics. conference series
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.21
H-Index - 85
eISSN - 1742-6596
pISSN - 1742-6588
DOI - 10.1088/1742-6596/1983/1/012052
Subject(s) - transformer , relay , hvdc converter , tap changer , power flow , engineering , electrical engineering , computer science , voltage , electric power system , power (physics) , physics , quantum mechanics
HVDC converter transformer oil-flow relay plays an important role in realizing non-power protection of converter transformer on-load tap changer, which can act accurately and directly affect the safe and stable operation of the whole HVDC program as well as the converter transformer itself. In this paper, the research revolves the hidden dangers of HVDC converter transformer and its identification. The paper begins with the analysis of the converter transformer operating principles of two German companies: MR and EMB. Then, the current application status and related inspection requirements of oil-flow relay are expounded. Finally, pertinent hidden danger identification and modification schemes are provided based on analysis of the danger in actual operation of oil-flow relay and its causes. The feasibility and effectiveness of the scheme are verified by the actual operation on site.