Research on CIGRE benchmark model and improved DC control strategy
Author(s) -
Yang Han,
Ke Liu,
Xuan Wang,
Keshan Che,
Yujie Ding,
Wei Yang
Publication year - 2020
Publication title -
journal of physics. conference series
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.21
H-Index - 85
eISSN - 1742-6596
pISSN - 1742-6588
DOI - 10.1088/1742-6596/1633/1/012080
Subject(s) - benchmark (surveying) , control system , computer science , control (management) , software , constant (computer programming) , mode (computer interface) , control theory (sociology) , engineering , electrical engineering , geodesy , artificial intelligence , geography , programming language , operating system
The safe and stable operation of the HVDC transmission system greatly depends on the control system. The DC control system realizes a series of control strategies such as constant-current, constant-voltage, and constant-extinction angle control by controlling the trigger phase. The CIGRE Benchmark model is often used as a standard test model for research, but it is usually necessary to improve in actual project. First of all, taking the CIGRE Benchmark model as the research object, the DC control mode and basic control functions are introduced systematically. On this basis, the improved control strategy is studied. At the same time, PSCAD / EMTDC simulation software is used to build an improved control system model. The transient response of CIGRE Benchmark and improved control system is simulated and analyzed. Furthermore, the control mode conversion and control system response under different control strategies are studied.