Flashover voltage computation of porcelain insulators under positive polarity lightning impulse voltages
Author(s) -
Shanmugam Gowrishankar,
Kalapati Surendra,
Karakad Sunitha
Publication year - 2019
Publication title -
iet science, measurement and technology
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.418
H-Index - 49
eISSN - 1751-8830
pISSN - 1751-8822
DOI - 10.1049/iet-smt.2018.5605
Subject(s) - arc flash , insulator (electricity) , impulse (physics) , voltage , electrical engineering , polarity symbols , materials science , electric field , high voltage , electric power transmission , acoustics , engineering , breakdown voltage , physics , quantum mechanics
The porcelain ceramic insulators have been used for outdoor insulation applications for a long time due to their impressive electrical and mechanical properties. The lightning impulse withstand voltage and flashover voltage characteristics of the insulators are important for insulation coordination of transmission lines and substations. This study presents a computer‐based simulation methodology to determine the positive polarity lighting impulse flashover voltage of porcelain suspension and station post‐insulators. The flashover voltage is determined by evaluating the streamer inception, propagation and sustenance criteria along the suitable paths based on finite‐element‐method‐based electric field computation. The streamer propagation path is found through air along the dry arcing distance rather than along the creepage path of the insulator. The lightning impulse flashover voltage of suspension and post‐insulators are computed based on simulation. The comparison of computed results with the experimental results gives a good agreement between them.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here