Compensation scheme for secondary arc current on four‐circuit parallel transmission lines
Author(s) -
Zhang Xu,
Xu Zhenyu,
Gao Bo,
Xie Xiaorong,
Wang K.
Publication year - 2016
Publication title -
iet generation, transmission and distribution
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.92
H-Index - 110
eISSN - 1751-8695
pISSN - 1751-8687
DOI - 10.1049/iet-gtd.2015.1102
Subject(s) - compensation (psychology) , arc (geometry) , scheme (mathematics) , current (fluid) , electric power transmission , computer science , electronic engineering , transmission (telecommunications) , electrical engineering , telecommunications , engineering , mathematics , mechanical engineering , psychology , mathematical analysis , psychoanalysis
This study presents a novel capacitive coupling compensation scheme for 500 kV four‐circuit transposed parallel transmission lines. Using this scheme, the capacitive coupling between energised phase and faulted phases in four‐circuit can be fully compensated. Moreover, the secondary arc current can be limited to <10 A. On the basis of the new scheme, an optimal compensation scheme for every kind of maintenance state is also depicted. Performances of the proposed schemes are validated by real‐time digital simulator.