z-logo
open-access-imgOpen Access
Investigation of the sympathetic tripping problem in power systems with large penetrations of distributed generation
Author(s) -
Jennett Kyle I.,
Booth Campbell D.,
Coffele Federico,
Roscoe Andrew J.
Publication year - 2015
Publication title -
iet generation, transmission and distribution
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.92
H-Index - 110
eISSN - 1751-8695
pISSN - 1751-8687
DOI - 10.1049/iet-gtd.2014.0169
Subject(s) - tripping , reliability engineering , fault (geology) , inverter , computer science , clearance , power (physics) , electric power system , voltage , engineering , electrical engineering , circuit breaker , medicine , physics , quantum mechanics , seismology , urology , geology
This study contains an investigation into sympathetic tripping – the undesirable disconnection of distributed generators (DGs) (in accordance with the recently‐introduced G83/2 under voltage protection) when a network fault occurs in the vicinity of the DG and is not cleared quickly enough by the network protection (i.e. before the DG's under voltage protection operates). An evaluation of the severity of and proposal of solutions to the problem of sympathetic tripping on a typical UK distribution power network is presented. An inverter model (as the majority of DGs will be inverter‐interfaced) that characterises the fault response of the inverter and its associated protection functions has been developed for use in simulation through exhaustive laboratory testing of a commercially‐available 3 kW inverter for DG application; the observed responses have been modelled and incorporated in a power system simulation package. It is shown, when using presently‐adopted DG interface and network protection settings, that the risk of sympathetic tripping is high in several future scenarios. To mitigate this risk, the impact of modifying network protection settings is evaluated. This study has two key findings – determination of the conditions at which the risk of sympathetic tripping is high and evaluation of a technique to mitigate this risk.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here