z-logo
open-access-imgOpen Access
Synchronised data‐based adaptive backup protection for series compensated line
Author(s) -
Sarangi Saumendra,
Pradhan Ashok Kumar
Publication year - 2014
Publication title -
iet generation, transmission and distribution
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.92
H-Index - 110
eISSN - 1751-8695
pISSN - 1751-8687
DOI - 10.1049/iet-gtd.2013.0820
Subject(s) - backup , series (stratigraphy) , computer science , line (geometry) , reliability engineering , engineering , mathematics , database , paleontology , geometry , biology
Metal oxide varistor (MOV) protected series capacitor, when present in a fault loop, modulates the impedance seen by the relay. With series capacitor placed away from the relay, the information on the level of compensation is required for proper protection decision by distance relay. In this study, synchronised data obtained at both ends are applied to calculate the compensation level which is used to adapt the relay setting for backup protection of adjacent line. The mutual coupling in the compensation portion is also considered in the apparent impedance computation. The status of capacitor during fault (bypassed or not) is obtained through impedance calculation during fault and the relay setting is adapted accordingly. Using data simulated through EMTDC/PSCAD for a series compensated line the technique is tested and found to be accurate.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here