Investigation on new mitigation method for lightning overvoltages in high‐voltage power substations
Author(s) -
Kuczek Tomasz,
Stosur Mariusz,
Szewczyk Marcin,
Piasecki Wojciech,
Steiger Martin
Publication year - 2013
Publication title -
iet generation, transmission and distribution
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.92
H-Index - 110
eISSN - 1751-8695
pISSN - 1751-8687
DOI - 10.1049/iet-gtd.2012.0190
Subject(s) - overvoltage , surge arrester , emtp , lightning (connector) , matlab , voltage , electrical engineering , engineering , electric power system , filter (signal processing) , surge , high voltage , power (physics) , electronic engineering , computer science , physics , quantum mechanics , operating system
In the present study, simulations of the lightning overvoltages propagation phenomenon in a typical 380 kV SF6 gas‐insulated substation are presented. Influence of surge arresters installation on maximum‐generated overvoltage peak values is illustrated. A new overvoltage mitigating passive device in a form of a high‐voltage (HV) L–C filter is proposed. A process of its development and research is explained along with a simulation results. As demonstrated, the proposed device can be used in HV networks as an alternative or additional improvement for lightning overvoltages mitigation purposes. All simulations have been conducted using Matlab Simulink as well as EMTP/ATP software packages