Premium
A study on fire behaviour of combustible components of two commonly used photovoltaic panels
Author(s) -
Chow C. L.,
Han S. S.,
Ni X. M.
Publication year - 2016
Publication title -
fire and materials
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.482
H-Index - 58
eISSN - 1099-1018
pISSN - 0308-0501
DOI - 10.1002/fam.2366
Subject(s) - cone calorimeter , thermogravimetric analysis , environmental science , fire retardant , materials science , smoke , flammability , composite material , waste management , photovoltaic system , forensic engineering , engineering , chemical engineering , char , pyrolysis , electrical engineering
Summary Photovoltaic (PV) modules are installed in some modern buildings for generating renewable energy. When a building catches fire, burning PV panels can contribute to an already very hazardous environment. Two common polycrystalline silicon PV samples A and B were selected with their chemical composition analysed by the Fourier transform infrared spectroscopy with justification by X‐ray photoelectron spectroscopy results. Sample A was confirmed to be a silicate product with polyurethane adhesive, and sample B has epoxy resin and is likely to have flame retardant as claimed. Thermal analysis by heating the samples was carried out using thermogravimetric analysis and thermogravimetric analysis coupled with infrared spectroscopy. The fire behaviour was then studied by a cone calorimeter under radiative heat fluxes from 10 to 70 kWm −2 . Three key parameters representing flashover propensity, total heat release per unit area and smoke toxicity hazard were obtained from the cone calorimeter tests for ranking the thermal and smoke hazards. The thermal hazards of both PV samples are low, at least during the early stage of a fire without flame acting directly on the sample. However, vast quantities of smoke were emitted from burning PV panels under high heat fluxes. Copyright © 2016 John Wiley & Sons, Ltd.