Subject(s) - islanding , inverter , harmonic , interconnection , signal (programming language) , voltage , electronic engineering , grid , computer science , electrical engineering , engineering , physics , distributed generation , acoustics , telecommunications , mathematics , geometry , renewable energy , programming language
We propose the islanding detection method using harmonic current as active signal. The active signal can be injected in the suppressed direction of the harmonic voltage during grid interconnection. On the other hand, the active signal is injected in the synchronized direction of the harmonic voltage due to the loads during islanding operation. As the result, the harmonic voltage is increased and the islanding operation is detected within 0.2 seconds. We have developed the single phase inverter for grid‐interconnection of low voltage with these functions and performed the experimental verification.