SUMMARY In the disconnecting switch of 300 kV or less single pole structure, the Great East Japan Earthquake received much damage at the former by the rotation insulator base metal which damage experience had. Conventionally, we carried out a simple desk evaluation about earthquake‐proof evaluation of insulator base metal. However, there is deviation with the damage actual condition and it became clear that it was an apparatus weak point part. Then, we worked on the analysis accuracy improvement of insulator base metal, and we built the analysis technology of the single pole structured disconnecting switch.