A Study on the Regional Energy Conservation Effects of a Multi-stage Outdoor Air Enabled Cooling System in a Data Center
Author(s) -
Moon-Ki Park,
Hyun-Jae Chang
Publication year - 2017
Publication title -
journal of the korean solar energy society
Language(s) - English
Resource type - Journals
eISSN - 2508-3562
pISSN - 1598-6411
DOI - 10.7836/kses.2017.37.1.071
Subject(s) - environmental science , energy conservation , data center , energy consumption , humidity , range (aeronautics) , air temperature , water cooling , meteorology , cooling load , evaporative cooler , engineering , air conditioning , geography , computer science , mechanical engineering , electrical engineering , aerospace engineering , operating system
A Data center houses a large number of server computers, storage and etc in racks. With the rapid increase of heat generation rates per rack in a data center, energy consumption rates for cooling have been increased year by year. In this study, energy conservation effects of a MOA (multi-stage outdoor air enabled) cooling system in a data center has been investigated when it is applied to 5 different locations, Korea. As results, Energy conservation effects of the MOA cooling system was achieved at about 20% to 30%. Humidifier operation time was 40 to 55 days when supply air temperature was maintained at 13, and humidity condition was kept within the allowed range even though humidifier was off. Furthermore, humidification was not needed when supply air temperature was maintained at 25°C. In selected 5 locations in Korea, the difference of regional climatic conditions affected no more than 5% in cooling energy consumption rates.
Accelerating Research
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom
Address
John Eccles HouseRobert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom