z-logo
open-access-imgOpen Access
The feasibility study for the building integrated geothermal system using the horizontal heat exchanger
Author(s) -
Hobyung Chae,
Yujin Nam,
Sung-Hoon Yoon
Publication year - 2015
Publication title -
journal of the korean solar energy society
Language(s) - English
Resource type - Journals
eISSN - 2508-3562
pISSN - 1598-6411
DOI - 10.7836/kses.2015.35.1.081
Subject(s) - heat exchanger , geothermal gradient , petroleum engineering , environmental science , architectural engineering , geology , engineering , mechanical engineering , geophysics
Recently, in order to prevent increasing energy usages in the international community, many countries have attempted to develop the innovative renewable energy systems. Among the renewable energy systems, Ground source heat pump(GSHP) system which supply the heating, cooling and hot water in the building has been attracted by its stability of heat production and high efficiency. However, the initial drilling costs become very expensive and the construction period takes longer the other systems, because GSHP system needs more than 100 m depth drilling. In this study, in order to reduce initial costs of the GSHP, the building integrated geothermal system using the horizontal heat exchanger was developed. The heating and cooling load in the standard housing model was calculated by a simulation and the system design capacity in the high-rise apartment was decided by the total load. Based on the system design capacity, the high-rise apartments were applied to a BIGS and vertical GSHP system and there are analyzed about initial costs. In the result, the initial cost of BIGS could reduce 24% of the initial cost of the vertical GSHP system.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here
Accelerating Research

Address

John Eccles House
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom