Evaluation on Reducing Peak Cooling Load Based on Dynamic Load Model of Building Perimeter Zones
Author(s) -
Kyoungho Lee,
James E. Brau
Publication year - 2011
Publication title -
journal of the korean solar energy society
Language(s) - English
Resource type - Journals
eISSN - 2508-3562
pISSN - 1598-6411
DOI - 10.7836/kses.2011.31.4.001
Subject(s) - cooling load , environmental science , perimeter , peak load , thermal , heat load , structural engineering , meteorology , nuclear engineering , engineering , mechanical engineering , mathematics , geometry , air conditioning , physics , thermodynamics
In this paper, inverse building modeling was applied to building perimeter zones which have different window orientation. Two test zones of east-facing and west-facing zones in ERS(Energy Resource Station) building, which is representative of small commercial building, was used to test performance of cooling load calculation and peak cooling load reduction. The dynamic thermal load model for the east and west zone was validated using measured data for the zones and then it was used to investigate the effect of peak cooling load reduction by adjustment of indoor cooling temperature set points during on-peak time period. For the east zone, the peak load can be reduced to about 60% of the peak load for conventional control even without any precooling. For the west zone, PLR is nearly independent of the start of the on-peak period until a start time of 1pm. Furthermore, PLR has a small dependence on the precooling duration. Without any precooling, the peak cooling load can be reduced to about 35% of the peak load associated with conventional control.
Accelerating Research
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom
Address
John Eccles HouseRobert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom