The Calculation Method of Shielding Coefficient of Neutral Line against an Induced Voltage by an Aerial Power Distribution Line Reflecting the Principle of Earth Return Current
Author(s) -
Sang-Mu Lee
Publication year - 2016
Publication title -
journal of the korea academia-industrial cooperation society
Language(s) - English
Resource type - Journals
eISSN - 2288-4688
pISSN - 1975-4701
DOI - 10.5762/kais.2016.17.7.86
Subject(s) - electromagnetic shielding , line (geometry) , voltage , power (physics) , physics , ground , mechanics , shielding effect , computational physics , electrical engineering , mathematics , engineering , geometry , thermodynamics , quantum mechanics
To solve the problem of the excessive error caused by using a single value for the shielding effect of the neutral line of an electric power distribution line in the calculation of the voltage it induces in a telecommunication line, the general expression that was previously developed to reflect the mechanism of voltage induction by a distribution line with multiple grounds is employed in this paper to represent the relationship between the leakage current rates at each ground pole. In this way, the formula for calculating the shielding effect of the neutral line can be factorized against the unbalanced current flowing in the neutral line, which is the root current of induction. This shielding coefficient of the neutral line is not constant, but can vary when a range of induced voltages is generated in the whole power distribution line. The calculation method developed herein reduces the error rate to one tenth of that of the existing calculation result in the case of overestimation and increases it by 14% in the case of underestimation.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here
Accelerating Research

Address

John Eccles House
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom