Research on Numerical Simulation of 3D Leakage Magnetic Field and Short-circuit Impedance of Axial Dual-low-voltage Split-winding Transformer
Author(s) -
Yan Li,
Longnv Li,
Yongteng Jing,
Fangxu Han
Publication year - 2013
Publication title -
energy and power engineering
Language(s) - English
Resource type - Journals
eISSN - 1949-243X
pISSN - 1947-3818
DOI - 10.4236/epe.2013.54b208
Subject(s) - leakage inductance , transformer , leakage (economics) , electrical impedance , electrical engineering , materials science , voltage , mechanics , electronic engineering , engineering , physics , economics , macroeconomics
It is difficult to accurately calculate the short-circuit impedance, due to the complexity of axial dual-low-voltage split-winding transformer winding structure. In this paper, firstly, the leakage magnetic field and short-circuit impedance model of axial dual-low-voltage split-winding transformer is established, and then the 2D and 3D leakage magnetic field are analyzed. Secondly, the short-circuit impedance and split parallel branch current distribution in different working conditions are calculated, which is based on field-circuit coupled method. At last, effectiveness and feasibility of the proposed model is verified by comparison between experiment, analysis and simulation. The results showed that the 3D analysis method is a better approach to calculate the short-circuit impedance, since its analytical value is more closer to the experimental value compared with the 2D analysis results, the finite element method calculation error is less than 2%, while the leakage flux method maximum error is 7.2%.
Accelerating Research
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom
Address
John Eccles HouseRobert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom