Closed loop cooling operation with MICON
Author(s) -
García Navarro
Publication year - 1995
Language(s) - English
Resource type - Reports
DOI - 10.2172/80948
Subject(s) - operability , loop (graph theory) , interlock , closed loop , water cooling , terminal (telecommunication) , engineering , nuclear engineering , simulation , computer science , mechanical engineering , control engineering , reliability engineering , telecommunications , mathematics , combinatorics
This Operability Test Procedure (OTP) provides instructions for testing the Closed Loop Cooling System interface with the MICON Terminal at the Plutonium Finishing Plant located at the 200 West Area of the Hanford Site. The Closed Loop Cooling System consists of several primary loops and a single secondary cooling loop. The test objectives are to functionally prove the interlocks and instruments of the closed loop cooling system with the MICON and to show operability of the system from the MICON Terminal. Any out of tolerance readings during the test will be adjusted immediately or with a new calibration package at a later time per cognizant engineers direction