242-A MCS Logic Acceptance Test Report for Year 2000 Upgrade
Author(s) -
M.C. Teats
Publication year - 1999
Language(s) - English
Resource type - Reports
DOI - 10.2172/797664
Subject(s) - upgrade , acceptance testing , test (biology) , computer science , software engineering , operating system , geology , paleontology
242-A Evaporator distributive control system upgrade to D/3 version 9.0-2 for year 2000 compliance. Testing was performed per test procedure HNF-3568. There were no unresolved exceptions. The system responded correctly to all testing and meets the requirements to operate the 242-A This report documents the acceptance test results for the Evaporator facility