THERMAL DISTRIBUTION SYSTEM EXPERIMENT
Author(s) -
R.F. Krajewski,
J.W. Andrews,
Wei Gao
Publication year - 1999
Publication title -
osti oai (u.s. department of energy office of scientific and technical information)
Language(s) - English
Resource type - Reports
DOI - 10.2172/759022
Subject(s) - instrumentation (computer programming) , ashrae 90.1 , data acquisition , experimental data , simulation , environmental science , computer science , engineering , meteorology , statistics , physics , mathematics , operating system
A laboratory experiment has been conducted which tests for the effects of distribution system purging on system Delivery Effectiveness (DE) as defined in ASHRAE 152P. The experiment is described in its configuration, instrumentation, and data acquisition system. Data gathered in the experiment is given and discussed. The results show that purging of the distribution system alone does not offer any improvement of the system DE. Additional supporting tests were conducted regarding experimental simulations of buffer zones and bare pipe and are also discussed