Operational test report for 241-AW tank inlet air control stations
Author(s) -
Westinghouse Hanford Minteer D.J.
Publication year - 1996
Language(s) - English
Resource type - Reports
DOI - 10.2172/659220
Subject(s) - flammable liquid , inlet , environmental science , marine engineering , control valves , storage tank , engineering , flow (mathematics) , current (fluid) , petroleum engineering , butterfly valve , leakage (economics) , waste management , mechanical engineering , electrical engineering , mechanics , physics , economics , macroeconomics
This document reports the results of operational testing on tank inlet air control stations in 241-AW tank farm. An air control station was installed on each of the six AW tanks. Operational testing consisted of a simple functional test of each station`s air flow controller, aerosol testing of each station`s HEPA filter, and final ventilation system balancing (i.e., tank airflows and vacuum level) using the air control stations. The test was successful and the units were subsequently placed into operation