Source term evaluation for UF{sub 6} release event in feed facility at gaseous diffusion plants
Author(s) -
Seong-Hwan Kim,
R.P. Taleyarkhan
Publication year - 1997
Publication title -
osti oai (u.s. department of energy office of scientific and technical information)
Language(s) - English
Resource type - Reports
DOI - 10.2172/631151
Subject(s) - wind speed , diffusion , environmental science , meteorology , aerosol , chemistry , atmospheric sciences , physics , thermodynamics
An assessment of UF{sub 6} release accidents was conducted for the feed facility of a gaseous diffusion plant (GDP). Release rates from pig-tail connections were estimated from CYLIND code predictions, whereas, MELCOR was utilized for simulating reactions of UF{sub 6} with moisture and consequent transport of UO{sub 2}F{sub 2} aerosols and HF vapor through the building and to the environment. Two wind speeds were utilized. At the high end (Case 1) a wind speed of {approximately} 1 m/s (200 fpm) was assumed to flow parallel to the building length. At the low end (Case 2) to represent stagnant conditions a corresponding wind speed of 1 cm/s (2 fpm) was utilized. A further conservative assumption was made to specify no closure of crane and train doors at either end of the building. Relaxation of this assumption should provide for additional margins. Results indicated that, for the high (200 fpm) wind speed, close to 66% of the UO{sub 2}F{sub 2} aerosols and 100% of the HF gas get released to the environment over a 10-minute period. However, for the low (2 fpm) wind speed, negligible amount ({approximately} 1% UO{sub 2}F{sub 2}) of aerosols get released even over a 2 hour period
Accelerating Research
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom
Address
John Eccles HouseRobert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom