z-logo
open-access-imgOpen Access
VPP--DESIGN CRITERIA FOR AN INSTALLATION TO REMOVE HYDROGEN FLUORIDE AND FLUORINE FROM THE CELLS 1 AND 2 VENTILATION GASES PRIOR TO FILTRATION
Author(s) -
J B Ruch
Publication year - 1950
Publication title -
osti oai (u.s. department of energy office of scientific and technical information)
Language(s) - English
Resource type - Reports
DOI - 10.2172/4166463
Subject(s) - data scrubbing , scrubber , nozzle , hydrogen fluoride , fluoride , baffle , fluorine , chemistry , waste management , engineering , inorganic chemistry , chemical engineering , mechanical engineering , organic chemistry
Criteria are presented for a horizontal cocurrent spray nozzle scrubbing system designed to remove fluorine and hydrogen fluoride from the 3000 cfm of ventilation air passing through the Volatility Pilot Plant. A reduction of fluorine concentration from 1520 to <2 ppm during a total release of 68 lbs, and a reduction of hydrogen fluoride concentration from 4090 to <1 ppm during a total release of 200 lbs, will adequately protect the Fiberglas media filters. Six scrubbing states each containing four nozzle-throat spray units are needed with a 5 to 10% aqueous caustic potash recycle system pumping at a maximum rate of approximately 180 gal/min, with a range per nozzle from 3 to 7 gal/min. The scrubber will be 4 ft x 4 ft x approximately 25 ft, containing a deentrainment section of baffles and demister. The associated ventilation system hardware, services, and instrumentation requirements are given. (auth

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here
Accelerating Research

Address

John Eccles House
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom