Test plan for evaluation of primary exhaust ventilation flow meters for double shell hydrogen watch list tanks
Author(s) -
W.E. Willingham
Publication year - 1996
Language(s) - English
Resource type - Reports
DOI - 10.2172/325289
Subject(s) - airflow , environmental science , ventilation (architecture) , marine engineering , waste management , storage tank , engineering , meteorology , mechanical engineering , physics
This document is a plan for testing four different flow meters for use in the primary exhaust ventilation ducts of Double Shell Tanks on the hydrogen watch list that do not already have this capability. This currently includes tanks 241-AW-101, 241-AN-103, 241-AN-104, 241-AN-105, and 241-SY-103. The anticipated airflow velocity in these tanks range from 0.25 m/s(50 ft/min) to 1.78 m/s (350 ft/min). Past experiences at Hanford are forcing the evaluation and selection of instruments to be used at the low flow and relatively high humidity conditions found in these tanks. Based on the results of this test, a flow meter shall be chosen for installation in the primary exhaust ventilation ducts of the above mentioned waste tanks