New flow boiling heat transfer correlation for CFC-114 and C{sub 4}F{sub 10}
Author(s) -
A.J. Szady
Publication year - 1995
Language(s) - English
Resource type - Reports
DOI - 10.2172/106515
Subject(s) - heat transfer , boiling , coolant , superposition principle , boiling heat transfer , thermodynamics , flow (mathematics) , transfer (computing) , mathematics , nucleate boiling , chemistry , heat transfer coefficient , mechanics , materials science , physics , computer science , parallel computing , mathematical analysis
The flow boiling tests being conducted at Cudo Technologies, Ltd. in Lexington, Kentucky are a part of The GDP Coolant Replacement Project. The tests are to be done with two alternates, C{sub 4}F{sub 10} and C{sub 4}F{sub 8}, as well as CFC-114. So far, tests were conducted with CFC-114 and C{sub 4}F{sub 10}. The CFC-114 data by Cudo shows better heat transfer performance than that predicted by the codes used in the numerical model which were based on a superposition model. The data was applied to an asymptotic model developed by Steiner and Taborek. The new correlation developed seems to fit better with the Cudo data as well as the Paducah cell test data. The model will be further investigated when C{sub 4}F{sub 8} data is available