Analysis of Voltage Drop and Thermal Characteristics for Poor Connections at Electrical Connector of Circuit Breaker of Small Size Pulverizer below 5.5kW
Author(s) -
Sang Chul Kim
Publication year - 2015
Publication title -
journal of the korean society of safety
Language(s) - English
Resource type - Journals
eISSN - 2383-9953
pISSN - 1738-3803
DOI - 10.14346/jkosos.2015.30.3.26
Subject(s) - circuit breaker , pulverizer , cable gland , electrical engineering , voltage drop , voltage , drop (telecommunication) , signal (programming language) , high voltage , short circuit , materials science , engineering , automotive engineering , mechanical engineering , computer science , grinding , programming language
This paper describes the characteristics of voltage drop and thermal for poor connection on electrical connector of circuit breaker in control box of small size pulverizer. In order monitor, we did the changes of RMS in voltage and temperature value with video and made normal state over 2.5N.m and poor connections state below 0.2N.m by screw gage. In case of voltage signal, the voltage drop was increased when the current was increased due to poor connections. In case of temperature signal, the temperature difference indicates ten times at 5A and fourteen times at 15A in the normal state. According to increase thermal energy, the insulation of electrical wiring and connector of circuit breaker can be carbonized. The results of this study will be useful to the development of preventive devices and system for electric fire by poor connection at small size pulverizer.
Accelerating Research
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom
Address
John Eccles HouseRobert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom