z-logo
open-access-imgOpen Access
Transformer Magnetizing Inrush Currents Using a Directly Coupled Voltage-Source Inverter
Author(s) -
Rickard Ekström,
Senad Apelfröjd,
Mats Leijon
Publication year - 2013
Publication title -
isrn electronics
Language(s) - English
Resource type - Journals
ISSN - 2090-8679
DOI - 10.1155/2013/361643
Subject(s) - inrush current , transformer , tripping , electrical engineering , relay , voltage , control theory (sociology) , engineering , computer science , power (physics) , physics , circuit breaker , control (management) , quantum mechanics , artificial intelligence
The connection of a power transformer to the grid is associated with magnetizing inrush currents that may result in power quality issues as well as faulty relay tripping. In distributed generation, the transformer may instead be premagnetized from the source to avoid this. In this paper, a VSI is directly coupled to a transformer. Three different strategies of premagnetization are implemented into the control system, and the inrush currents are measured for various values of the remanent flux in the core. The results show good reduction in the peak magnetizing inrush currents without using any external circuitry.

The content you want is available to Zendy users.

Already have an account? Click here to sign in.
Having issues? You can contact us here
Accelerating Research

Address

John Eccles House
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom