Experimental Investigation of Embedded Micropin-Fins for Single-Phase Heat Transfer and Pressure Drop
Author(s) -
Chirag R. Kharangate,
Ki Wook Jung,
Sangwoo Jung,
Daeyoung Kong,
Joseph Schaadt,
Madhusudan Iyengar,
Chris Malone,
Hyoungsoon Lee,
Mehdi Asheghi,
Kenneth E. Goodson
Publication year - 2018
Publication title -
journal of electronic packaging
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.523
H-Index - 52
eISSN - 1528-9044
pISSN - 1043-7398
DOI - 10.1115/1.4039475
Subject(s) - nusselt number , pressure drop , fin , materials science , heat transfer , reynolds number , mechanics , thermodynamics , drop (telecommunication) , composite material , mechanical engineering , physics , turbulence , engineering
Three-dimensional (3D) stacked integrated circuit (IC) chips offer significant performance improvement, but offer important challenges for thermal management including, for the case of microfluidic cooling, constraints on channel dimensions, and pressure drop. Here, we investigate heat transfer and pressure drop characteristics of a microfluidic cooling device with staggered pin-fin array arrangement with dimensions as follows: diameter D1⁄4 46.5 lm; spacing, S 100 lm; and height, H 110 lm. Deionized singlephase water with mass flow rates of _ m1⁄4 15.1–64.1 g/min was used as the working fluid, corresponding to values of Re (based on pin fin diameter) from 23 to 135, where heat fluxes up to 141 W/cm are removed. The measurements yield local Nusselt numbers that vary little along the heated channel length and values for both the Nu and the friction factor do not agree well with most data for pin fin geometries in the literature. Two new correlations for the average Nusselt number ( Re) and Fanning friction factor ( Re ) are proposed that capture the heat transfer and pressure drop behavior for the geometric and operating conditions tested in this study with mean absolute error (MAE) of 4.9% and 1.7%, respectively. The work shows that a more comprehensive investigation is required on thermofluidic characterization of pin fin arrays with channel heights Hf< 150 lm and fin spacing S1⁄4 50–500 lm, respectively, with the Reynolds number, Re< 300. [DOI: 10.1115/1.4039475]
Accelerating Research
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom
Address
John Eccles HouseRobert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom