Subject(s) - emtp , surge arrester , surge , engineering , lightning arrester , voltage , electrical engineering , electric power system , physics , quantum mechanics , power (physics)
This paper describes simplified modeling of metal oxide surge arrester (MOSA) to operate analysis. This model is a new model proposed (P-K Model) to verify the accuracy in order to compare with IEEE and Pinceti Model. The simulations are performed with the Alternative Transients Program version of Electromagnetic Transient Program (ATP-EMTP). In the present paper, the MOSA models were verified for several medium voltages which consist of 18kV and 21kV, which 18kV arrester was used in 22kV system of Provincical Electricity Authority (PEA) and 21kV arrester was used in 24kV system of Metropolitan Electricity Authority (MEA) in Thailand. The P-K model was evaluate from different manufacturing, it is based on the General Electric (GE), Siemens and Ohio Brass as well as IEEE and Pinceti Model. The tests are performed by applying a fast front current surge with front time of up to 0.5μs and the standard impulse current surge (8/20μs). The results were compared between three models in order to calculate the error operation of the MOSA in the ATP-EMTP Program. The relative error of arrester models show that the P-K model can be used to simulate and calculate in ATP-EMTP program as well as IEEE and Pinceti model. In the case of fast front current surge, the P-K model has a maximum error of 5.39% (Ohio Brass, 10 kA, 21kV) and has a minimum error of 0.24% (GE, 10 kA, 18kV). Also, the standard impulse current surge, P-K model has a maximum error of 2% (Ohio Brass, 10 kA, 18kV) and has a minimum error of 0.32% (Siemens, 10 kA, 21kV) in the voltage response
Accelerating Research
Robert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom
Address
John Eccles HouseRobert Robinson Avenue,
Oxford Science Park, Oxford
OX4 4GP, United Kingdom