Premium
Current densities and total contact currents during forest clearing tasks under 400 kV power lines
Author(s) -
Korpinen Leena,
Kuisti Harri,
Elovaara Jarmo
Publication year - 2016
Publication title -
bioelectromagnetics
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.435
H-Index - 81
eISSN - 1521-186X
pISSN - 0197-8462
DOI - 10.1002/bem.21980
Subject(s) - bioelectromagnetics , clearing , environmental science , current (fluid) , sample (material) , power (physics) , electric power , physics , electrical engineering , engineering , business , electromagnetic field , finance , quantum mechanics , thermodynamics
The aim of the study was to analyze all values of electric currents from measured periods while performing tasks in forest clearing. The objective was also to choose and analyze measurement cases, where current measurements successfully lasted the entire work period (about 30 min). Two forestry workers volunteered to perform four forest clearing tasks under 400 kV power lines. The sampling frequency of the current measurements was 1 sample/s. The maximum values of the current densities were 1.0–1.2 mA/m 2 (calculated internal EFs 5.0–12.0 mV/m), and the average values were 0.2–0.4 mA/m 2 . The highest contact current was 167.4 μA. All measured values during forest clearing tasks were lower than basic restrictions (0.1 V/m and 0.8 V/m) of the International Commission on Non‐Ionizing Radiation Protection. Bioelectromagnetics. 37:423–428, 2016. © 2016 The Authors. Bioelectromagnetics published by Wiley Periodicals, Inc.