Possible efficiency improvement by application of various operating regimes for the cooling water pump station at thermal power plant - Bitola
Author(s) -
Vladimir Mijakovski,
Vangelče Mitrevski,
Nikola Mijakovski
Publication year - 2011
Publication title -
thermal science
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.339
H-Index - 43
eISSN - 2334-7163
pISSN - 0354-9836
DOI - 10.2298/tsci110316133m
Subject(s) - condenser (optics) , power station , cooling tower , thermal power station , environmental science , electricity , water cooling , pipeline (software) , power (physics) , nuclear engineering , mechanical engineering , electrical engineering , engineering , physics , thermodynamics , light source , optics
Thermal power plant (TPP) - Bitola is the largest electricity producer in the Republic of Macedonia with installed capacity of 691 MW. It is a lignite fired power plant, in operation since 1982. Most of the installed equipment is of Russian origin. Power plant's cold end comprised of a condenser, pump station and cooling tower is depicted in the article. Possible way to raise the efficiency of the cold end by changing the operating characteristics of the pumps is presented in the article. Diagramic and tabular presentation of the working characteristics of the pumps (two pumps working in paralel for one block) with the pipeline, as well as engaged power for their operation are also presented in this article