Load Calculations of Radiant Cooling Systems for Sizing the Plant
Author(s) -
Eleftherios Bourdakis,
Ongun Berk Kazanci,
Bjarne W. Olesen
Publication year - 2015
Publication title -
energy procedia
Language(s) - English
Resource type - Journals
SCImago Journal Rank - 0.474
H-Index - 81
ISSN - 1876-6102
DOI - 10.1016/j.egypro.2015.11.333
Subject(s) - cooling load , radiant cooling , sizing , ceiling (cloud) , passive cooling , heat load , water cooling , nuclear engineering , environmental science , maximum temperature , simulation , engineering , mechanical engineering , thermal , structural engineering , air conditioning , meteorology , thermodynamics , physics , chemistry , organic chemistry
The aim of this study was, by using a building simulation software, to prove that a radiant cooling system should not be sized based on the maximum cooling load but at a lower value. For that reason six radiant cooling models were simulated with two control principles using 100%, 70% and 50% of the maximum cooling load. It was concluded that all tested systems were able to provide an acceptable thermal environment even when the 50% of the maximum cooling load was used. From all the simulated systems the one that performed the best under both control principles was the ESCS ceiling system. Finally it was proved that ventilation systems should be sized based on the maximum cooling load