Влияние массовой скорости на величину критического теплового потока при кипении деионизованной воды с недогревом в микроканальной системе охлаждения
Author(s) -
В.В. Кузнецов,
А.С. Шамирзаев
Publication year - 2018
Publication title -
pisʹma v žurnal tehničeskoj fiziki
Language(s) - English
Resource type - Journals
eISSN - 1726-7471
pISSN - 0320-0116
DOI - 10.21883/pjtf.2018.20.46809.17114
Subject(s) - subcooling , boiling , microchannel , materials science , boiling point , volumetric flow rate , thermodynamics , mass flow rate , chemistry , analytical chemistry (journal) , chromatography , physics
We have experimentally studied the influence of the mass flow rate on the critical heat flux (CHF) during the boiling of deionized water underheated relative to the saturation temperature in a microchannel cooling system. The experimental unit comprised a copper-based block with two 0.36-mm-deep microchannels of 2 mm width and 16 mm length. The mass flow rate ranged from 100 to 600 kg/(m^2 s) and the initial subcooling was varied from 30 to 70°C. It was found that the character of boiling crisis changed with increasing mass flow rate and the CHF significantly increased upon complete condensation of vapor in the distribution chamber of the cooling system.